    Product Description


    Pressure Switches are safety devices used in positive-pressure or differential-pressure systems to sense gas or air pressure systems.
    Features:
    • For use with natural gas, liquid propane (LP) gas, or air.
    • Diaphragm-actuated safety-limit switch.
    • Switch can be wired to turn on alarm.
    • C6097A models break control circuit at setpoint on pressure fall.
    • C6097B models break control circuit at setpoint on pressure rise.
    • Lockout with manual reset and recycle options.
    • Lockout models have external manual reset button.
    • Removable transparent cover protects scaleplate and adjusting knob.
    • Pipe tappings allow selection of positive pressure (air only) or venting connections (NPT mount only).
    • 1/4 in. NPT or flange mount models for direct mounting to Honeywell Integrated Valve Train.
    • Optional switch position indicator lamp available.
    • IP54 enclosure standard.
    • Ranges: 0.4 to 5 in.wc, 3 to 21 in.wc, 12 to 60 in.wc or 1.5 to 7 psi.
    • Surge orifice.
    • Integral vent limiter on all models.

    Specifications

    General Characteristics

    Specifications:
    ApplicationSafety devices used in positive-pressure or differential-pressure systems to sense gas or air pressure changes
    Dimensions (in.)3 17/32 in. high x 2 23/32 in. wide x 2 23/32 in. deep
    Dimensions (mm)90 mm high x 69 mm wide x 69 mm deep
    Mounting1/4 in. NPT internal thread
    Electrical RatingsIgnition Transformer: 540 VA, Pilot Valve: 50 VA. Main Valve: 400 VA with 2-1/2 times inrush
    Approvals, Underwriters Laboratories Inc.Component Listed, MP 2168-8-1
    Approvals, Canadian Standards AssociationFile # 95329 Certificate 2632-01
    Electrical ConnectionsScrew terminals
    Contact Ratings120 Vac Switch Contact-- 3.0 AFL, 18.0 ALR, 5.0 A resistive; 240 Vac Switch Contact-- 3.0 AFL, 18.0 ALR, 5.0 A resistive
    Operating Temperature Range (F)-40 F to +140 F
    Operating Temperature Range (C)-40 C to +60 C
    Approvals, Swiss REAcceptable
    Approvals, Factory MutualJI 2D4A1.AF
    Approvals, OthersCSD-1 AFB: Acceptable
    Operating Range (psi)0.4 to 5 in. wc
    Operating Range (kPa)0.10 to 1.25 kPa
    Differential Pressure Range (psi)max. 0.6 in. wc @ min. setpoint; max. 0.25 in. wc @ max. setpoint
    Differential Pressure Range (kPa)max. 0.15 kPa @ min. setpoint; max. 0.25 kPa @ max. setpoint
    Differential TypeAdditive
    Switch OperationManual Reset
    Switching ActionBreak on pressure fall
    Pipe ConnectionVent or Low pressure--1/8 in. NPT internal thread