DISCOUNTS FOR CONTRACTORS | Become a Trade Pro
DISCOUNTS FOR CONTRACTORS | Become a Trade Pro

(888) 405-6064

Cancel Call Text

Goodman GPG1442060M41 3.5 Ton 60k BTU 14 SEER Packaged Gas/Electric Unit

Item Code: 
GPG1442060M41

More Views

Originally $3,336.15 Click for price
You Save 13%

In Stock

Originally $3,336.15 Click for price
Availability: Ships in 3-5 business days.
Free shipping

Need it faster?

Give us a call (888) 405-6064
Are you a trade professional?

    Product Description

    Goodman 3.5 Ton (60,000 BTU) 14 SEER Packaged Gas/Electric Unit Energy-Efficient Compressor, 81% AFUE - GPG1442060M41

    A LOT GOES INTO EVERY GOODMAN® BRAND GPG14M PACKAGED UNITS

    The art of precision

    Efficient Cooling Capacity - 5 millimeter (select models) refrigeration grade premium copper tubing and aluminum fin condenser coil configuration delivers outstanding heat transfer properties.

    All-Aluminum Evaporator Coil - A single metal solution that is designed for enhanced durability and performance (select models).

    Goodman packaged units simply work the way they're suppose to, making each one a thing of beauty.

    Multi-Speed ECM Blower Motor - Provides quiet system startup and shutdown with highly-efficient performance.

    Refrigeration-Grade Premium Copper Tubing and Aluminum Fin Condenser Coil Configuration - Delivers outstanding heat transfer properties with R-410A refrigerant.

    Heavy-Gauge Galvanized Steel Enclosure with Powder-Paint Finish - Protects your system from extreme outdoor elements.

    Fully-Insulated Blower Compartment - Designed for quiet performance. Panels are conveniently located to provide easy access.

    Self-Contained Packaged Unit - Designed for multi-position installation.

    Standard Features

    • Durable, corrosion-resistant T-140 aluminized steel tubular heat exchanger
    • Energy-efficient compressor
    • All-aluminum evaporator coil
    • Aluminum tube/aluminum fin coil
    • Multi-speed ECM indoor blower motor
    • Flowrater expansion device on 2- to 4-ton units; TXV expansion device on 5-ton units
    • Redundant gas valve with easy conversion to propane
    • Power-assisted combustion Direct spark ignition system includes a microprocessor-based control for the entire ignition sequence, all blower operation, and all safety circuits complete with self-diagnostics
    • All models comply with California Low NOx standards
    • AHRI Certified; ETL Listed

    Cabinet Features

    • High-quality UV-resistant powder-paint finish
    • Horizontal or downflow application
    • Convenient access panels
    • One roof curb fits all units
    • Fully insulated cabinet
    • Bottom, 2" high base rails for easier handling
    • When properly anchored, meets 2010 Florida Building Code unit integrity requirements for hurricane-type winds (Anchor bracket kits available.)

    For information regarding our return policy, please click here.


    Specifications

    General Characteristics

    Cooling:
    Total BTU/h40,000
    Sensible BTU/h30,000
    SEER/EER14.0/11.0
    Decibels78
    AHRI Numbers7505449

     

    Heating Capacity:
    Input (BTU/hr)60,000
    Output (BTU/hr)48,000
    AFUE(%)81
    Temperature Rise Range (°F)30-60
    # of Bunners3
    Orifice Size(Natural/LP)45/1.25MM

     

    Evaporator Motor:
    TypeECM
    Wheel(D x W)10" x 9"
    Indoor Nominal CFM1,300
    Motor Speed Tap(Cooling)T4
    RPM/Amps(Cooling)1050/5.7
    Horsepower3/4

     

    Evaporator Coil:
    Face Area (ft²)4.3
    Rows/Fins per Inch4/14
    Position Size(Cooling)0.072
    Filter Size(ft²)/Drain Size(NPT)4.3
    Drain Size(NPT)3/4"
    Refrigerant CHarge(oz.)88

     

    Condenser Fan/Coil:
    Horsepower - RPM1/4-830
    Diameter / # of Blades22" / 3
    Outdoor Nominal CFM2,850
    Fase Area(ft²)11.1
    Rows Deep/Fins per Inch2/27

     

    Compressor:
    Quantity/Type1/Scroll
    StageSingle
    Compressor RLA/LRA17.9/112

     

    Electrical Data:
    Volts/Phaze/(60 Hz)208-230/1
    Indoor Blower FLA5.7
    Outdoor Fan FLA/LRA1.4/2.9
    Total Unit Amps22.3
    Minimum Circuit Ampacity26.8
    Maximum Overcurrent Protection40 amps
    Entrance Size Power Supply1 1/8"
    Entrance Size Control Voltage7/8"

     

    Weight:
    Operating/Shipping Weight(LBS)493/515

    1. Wire size should be determined in accordance with National Electrical Codes. Extensive wire runs will require larger wire sizes.
    2. Must use time-delay fuses or HACR-type circuit breakers of the same size as noted.
    Note: Always check the S&R plate for electrical data on the unit being installed.

    Reviews
    Product Questions

    Product Questions

    No questions yet. Be the first to ask the question!
    Shipping Calculator